Fire-resistant Performance: UL1581 VW-1
Dielectric Constant: UL854
Stability Factor: UL854
Bending Test: UL854
Executive Standard: UL854
Application
Mainly used as drop wire, equipment earth wire, deep well submersible pump wire in well casing and occasion stipulated in (NEC)1.4 - 1.8
Construction
Conductor: Stranded bare copper or tinned copper, electrical property & Structure in accordance with ASTMB33或ASTM B172 flexible conductor requirement
Insulation: ROHS thermosetting insulation material, , prior color black or as per customer’s request
Outer Sheath: ROHS thermosetting insulation material, , prior color black or as per customer’s request
Technical Specification
Nominal Voltage: 600V (AC)
Test Voltage
U=600V
18-10AWG U0=3000V 50HZ 1min
8-2AWG U0=3500V 50HZ 1min
1-4/0AWG U0=4000V 50HZ 1min
Temperature Rating: Working Temperature -40℃~+90℃, max conductor Temperature 125℃, Allowable short circuit temperature 200°C in 5 second
Service Life: Expected life span≥25 years
Productor Structure and Paramters
Size(AWG) | Conductor Construction(n/mm) | Finished Cable OD(mm) | Max DC Resistance(20℃)(Ω/km) |
14 | 41/0.254 | 5.8 | 8.96 |
12 | 65/0.254 | 6.2 | 5.64 |
10 | 105/0.254 | 6.8 | 3.546 |
8 | 168/0.254 | 9.0 | 2.23 |
6 | 266/0.254 | 10.1 | 1.403 |
4 | 420/0.254 | 11.5 | 0.882 |
2 | 665/0.254 | 13.3 | 0.5548 |
1 | 836/0.254 | 15.9 | 0.4398 |
1/0 | 1045/0.254 | 17.0 | 0.3487 |
2/0 | 1330/0.254 | 18.3 | 0.2766 |
3/0 | 1672/0.254 | 19.8 | 0.2194 |
4/0 | 2109/0.24 | 21.5 | 0.1722 |
Company:Jiukai Special Cable (Shanghai) Co., Ltd.
Contact:Ms. Ding
Tel:0086 021-57186991
Mobile:+86 13585832527
E-mail:daniel@jiukaicable.com
Address:No. 875, Puwei Highway Nanqiao Town, Fengxian District, Shanghai,China