语言选择: 中文版line 英文版

Solar Cable

  • Japanese Standard PSE Approved Solar Cable (HCV)
  • Japanese Standard PSE Approved Solar Cable (HCV)
  • Japanese Standard PSE Approved Solar Cable (HCV)

Japanese Standard PSE Approved Solar Cable (HCV)

  • Product Properties/Standards

    Fire-resistant Performance: JIS C 3005

    Low-Temperature Properties: JIS C 3005

    Gas Emission: JIS C 3666-2

    UV Resistant: JIS K 7350-1、2

    Flame Test: Self-extinguishing within 60s


  • Inquire Now

Application

Used in Nominal Voltage 600V(AC) solar power system.


Construction

Conductor: Stranded bare copper or tinned copper, electrical property & Structure in accordance with JIS C 3102 and JIS C 3152 flexible conductor requirement

Insulation: LSZH electron-beam cross-linked Polyolefin copolymer ROHS material, prior color black or as per customer’s request.

Outer Sheath: RoHS lead-free high-temperature-resistant PVC, prior color black or as per customer’s request.


Technical Specification

Nominal Voltage:  600V (AC)

Test Voltage: No breakdown at 1.5KA(AC) 50HZ 1min   20±5℃

Temperature Rating: Working Temperature -40℃~+90℃, max conductor Temperature 125℃, Allowable short circuit temperature 200°C in 5 second.

Service Life: Expected life span≥25 years

Bending Radius: Fixed installation>4D, Occasionally moved>5D


Productor Structure and Paramters

Size (n/mm2)Conductor Construction (n/mm)Finished Cable OD (mm)Max DC Resistance (Ω/km)(AC)Test Voltage(AC)
(20℃,  Bare Copper)(20℃, Tinned Copper)
1×2.07/0.65.79.249.631.5KV/1min
1×3.57/0.86.35.205.411.5KV/1min
1×5.57/1.07.03.333.471.5KV/1min
1×87/1.27.62.312.411.5KV/1min

PSE jse certification.png

japanese JSE Certification