Conductor : Finely stranded bare copper flexible conductor.
Insulation : Oil & water resistant thermoplastic rubber,
Sheath : Black heavy duty thermoplastic rubber.
Cable Shape: ROUND CABLES
FEATURES & PROPERTIES
Meets the requirement of CENELEC HD 22.1.S2, DIN
VDE 0282 PART 810, IEC 245, CEI 20-19 & BS 6007, BS 6899.
Designed for heavy duty use.
Cut, tear & abrasion resistant.
Exceptional long term performance.
Excellent resistant to oils, chemicals, ozone & solvents.
Excellent Impact Resistant.
Excellent Weather Resistant.
Performs & Looks like Vulcanize Rubber.
Excellent Electrical Properties.
APPLICATION
For continuous use in deep well to supply power to submersible pumps down to depths of 500 mtrs. Double sheathed round pump cables are better suited for heavy duty application like sewage, slurry and dewatering pumps. These conditions requires the sheathing to be able to with stand abrasion, prevent ingress of water along the interstices of the cable and be resistant to acidic fluids and chemicals.
CONSTRUCTION
Conductor : Finely stranded bare copper flexible conductor.
Insulation : Oil & water resistant thermoplastic rubber,
Sheath : Black heavy duty thermoplastic rubber.
JIUKAI 3CORE ROUND CABLES FOR SUBMERSIBLE PUMPS (1100 VOLTS) | |||||||
CONDUCTOR | RUBBER INSULATION | TOTAL THICKNESS OF DOUBLE RUBBER SHEATH | Conductor Resistance at 20°C (max) ohms/km | CURRENT Rating at 40°C Amps. | |||
Nominal Area in | Nos. & Dia.of wire | Nominal Thickness | Nominal Core Dia. | Nominal Thickness | Approx. Overall Dimensions | ||
Sq. mm. | Nos. / mm | mm | mm | mm | mm | ||
1.50 | 22/0.30 | 0.80 | 3.25 | 1.50 | 10.00 | 12.10 | 14 |
2.50 | 36/0.30 | 0.90 | 3.84 | 1.50 | 11.00 | 7.41 | 18 |
4.00 | 56/0.30 | 1.00 | 4.50 | 1.60 | 13.00 | 4.95 | 26 |
6.00 | 85/0.30 | 1.00 | 5.30 | 1.60 | 14.60 | 3.30 | 31 |
10.00 | 140/0.30 | 1.00 | 6.50 | 2.00 | 18.00 | 1.91 | 42 |
16.00 | 226/0.30 | 1.00 | 8.00 | 2.00 | 21.20 | 1.21 | 57 |
25.00 | 354/0.30 | 1.20 | 10.10 | 2.15 | 26.00 | 0.780 | 72 |
35.00 | 495/0.30 | 1.20 | 11.30 | 2.15 | 28.30 | 0.554 | 90 |
50.00 | 703/0.30 | 1.40 | 13.60 | 2.25 | 33.50 | 0.386 | 115 |
70.00 | 440/0.45 | 1.40 | 15.30 | 2.45 | 37.80 | 0.272 | 143 |
95.00 | 475/0.50 | 1.60 | 18.00 | 2.40 | 43.50 | 0.206 | 165 |
JIUKAI 4CORE ROUND CABLES FOR SUBMERSIBLE PUMPS (1100 VOLTS) | |||||||
CONDUCTOR | PVC INSULATION | TOTAL THICKNESS OF DOUBLE PVC SHEATH | Conductor Resistance at 20°C (max) ohms/km | CURRENT Rating at 40°C Amps. | |||
Nominal Area in | Nos. Dia.of wire | Nominal Thickness | Nominal Core Dia. | Nominal Thickness | Approx. Overall Dimensions | ||
Sq. mm | Nos. / mm | mm | mm | mm | mm | ||
1.50 | 22/0.30 | 0.80 | 3.25 | 1.50 | 10.80 | 12.10 | 14 |
2.50 | 36/0.30 | 0.90 | 3.84 | 1.65 | 12.50 | 7.41 | 18 |
4.00 | 56/0.30 | 1.00 | 4.50 | 1.65 | 14.10 | 4.95 | 26 |
6.00 | 85/0.30 | 1.00 | 5.30 | 1.65 | 16.00 | 3.30 | 31 |
10.00 | 140/0.30 | 1.00 | 6.50 | 2.00 | 20.35 | 1.91 | 42 |
16.00 | 226/0.30 | 1.00 | 8.00 | 2.00 | 23.40 | 1.21 | 57 |
25.00 | 354/0.30 | 1.20 | >10.10 | 2.20 | 28.80 | 0.780 | 72 |
35.00 | 495/0.30 | 1.20 | 11.50 | 2.20 | 31.50 | 0.554 | 90 |
50.00 | 703/0.30 | 1.40 | 13.60 | 2.30 | 37.30 | 0.386 | 115 |
70.00 | 440/0.30 | 1.40 | 15.30 | 2.60 | 42.20 | 0.272 | 143 |
95.00 | 475/0.50 | 1.60 | 18.00 | 2.65 | 48.80 | 0.206 | 165 |
Note :
1. The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360.
2. In view of continuous improvements in our design and process, specifications given here in are subject change without notice.
Company:Jiukai Special Cable (Shanghai) Co., Ltd.
Contact:Ms. Ding
Tel:0086 021-57186991
Mobile:+86 13585832527
E-mail:daniel@jiukaicable.com